The one phase power meter PCE-ND30 can be used to measure 54 parameters in a UI network. In addition to the performance measurement of the 1 phase power meter PCE-ND30, it can detect voltage, current, and harmonics up to the 51st order. The power display can be used as 1 or 3 phase. It does not matter if the connected load is balanced or unbalanced. All readings are displayed graphically on the display from the power meter. What measurement values are displayed, can be set by the user. This can be done in up to 10 groups with 8 measurement parameters. In addition to displaying the current measured values, the power display can also represent maximum and minimum values. 

Two built-up relays can be used for alarming at reduced or crossing borders. Optionally, the user still a 0/4 ... 20 mA analog output and two inputs for PT100 temperature sensors. Also, the power meter can be equipped with an 8 GB memory and Ethernet interface. The network interface can be accessed on a web interface and the memory of the performance indicator. On delivery the RS485 Modbus interface is installed, on the power meter can be programmed and read. 
- Measurement of all parameters from a U / I network - Measurement of harmonics up to 51th order 
- 2 x PT100 input optional 
- RS485 Modbus 
- Alarm relay and analog output 
- Web interface and data memory optional 
- Panel mounting 

 

Technical specifications
Measuring ranges
Power (Class 0.2) 
1 A AC 
5 A AC

0.1 ... 1.2 A  
0.5 ... 6.0 A  
max. Display Area: 20 kA
Voltage LN (Class 0.2) 
57.7 V AC 
230 V AC 
400 V AC

11.5 ... 70 V 
46 ... 276 V 
80 ... 480 V 
max. Display area: 480 kV
Voltage LL (Class 0.5) 
100 V AC 
400 V AC 
690 V AC

20 ... 120 V 
80 ... 480 V 
138 ... 830 V 
max. Display area: 830 kV
Active Power (Class 0.5) ± 1999.9 W 
max. Display range: ± 1999.9 MW
Reactive power (Class 1) ± 1999.9 Var 
max. Display range: ± 1999.9 MVar
Apparent power (Class 0.5) 0 ... 1999.9 Va 
max. Display range: 0 ... 1999.9 MVA
Active energy (Class 0.5) ± 1999,9Wh 
max. Display range: ± 1999.9 MWh
Reactive energy (class 1) ± 1999.9 Varh 
max. Display range: ± 1999.9 Mvarh
Apparent energy (Class 0.5) 0 ... 1999 VAh 
max. Display range: 0 ... 1999.9 MVAh
Active power factor -1 .... 1
Action bill money -1.2 ... 1.2
Frequency 45 ... 65 Hz
Harmonic distortion / Harmonic Distortion 0 ... 100%
Harmonics voltage and current up to 51. order 0 ... 100%
Additional Specifications
Temperature input (optional) 2 x 2-wire PT100 
-50 ... 400 ° C / -58 ... 752 ° F 
± 0.5% v. MB.
RS485 interface Modbus RTU  
8N2, 8E1, 8O1, 8N1 
address: 1 ... 247 
Baud rate: 4800, 9600.19200, 38400, 57600, 115200
Ethernet 10/100 Protocols: TCP, HTTP. FTP
display 3.5 "LCD 
320 x 240 pixels
dimensions 96 x 96 x 77 mm / 3.7 x 3.7 x 3 in
Panel Cutout 92.5 x 92.5
Weight 300 g / 10.5 oz
Protection Front: IP65 
connection side: IP20
Power supply 85 ... 253 V AC 
90 ... 300 V DC
Input 6 VA
Power loss Voltage side: 0.2 VA 
current side: 0.1 VA
Heating time 5 minutes
Operating conditions -10 ... 55 ° C / 0 ... 95% rh
Operating position Each
Overload Voltage: 2 x Un (5 seconds), 
current: 50 A (1 second).
Electromagnetic compatibility EN 61000-6-2 
EN 61000-6-4
Housing insulation Double to EN61010-1
Pollution degree  2
Insulation Category III